Apiste Precision Air PAU-AZ7000SE
Xuất sứ: Apiste
Nhà cung cấp: PITESCO Viet Nam
Hãng sản xuất: Apiste
Specifications
Cooling Method | Air-Cooled Type |
---|---|
Type | Temperature Controller (energy conservation) |
Cooling Capacity (W) | 6400/7200 |
Heating Capacity (W) | 9100/9900 |
Temperature Control Precision (°C) | +-0.1 |
Setting Temperature Range (°C) | 10~50 |
Use Area Temperature (°C) | -5-35 (change in temperature gradient: within 1°C/1h) |
Use Area Humidity (%RH) | 15-85(change in temperature gradient: within 5%/1h) (No condensation) |
Processed Air Volume (m2/min)(50Hz) | 20/22 |
External Dimensions(mm) | H1631×W650×D800 |
Volume (kg) | 220 |
Coating Color | Ivory(JPMA: Semi-gloss Y22-85B) |
Blower Duct Connection Diameter (mm) | φ200 with damper |
Rated Voltage (V) | Three-phase AC200 |
Consumption Current (A) | 11/12.5 |
Wattage (W) | 3000/4000 |
Drain Discharge Water Connection Diameter (mm) | 20A Female socket (Rp3/4) |
Coolant | R-407c 1700g |
Exhaust Air Volume (m3/min) | 33/39 |
Safety Circuit/Main Circuit | Earth leakage circuit breaker (20A 30mA) |
Safety Circuit/Blower | Overcurrent relay, delay timer (3 minutes), surge absorber |
Safety Circuit/Compressor | Low temperature thermostat driving prevention, overcurrent relay, motor protectors, surge absorber |
Output/Main Unit Malfunction Output | No-voltage contact a (AC250V / 2A / Resistive load) |
Output/Temperature Control Top-Bottom Limit Alarm | No-voltage contact a (AC250V / 2A / Resistive load) |
Parts list supplied
Anchor Mount | 2 |
---|---|
INSULOK Tie | 2 |
User Manual | 1 |
Optional Parts List
Duct Set | o |
---|---|
Return Chamber | o |
Exhaust Chamber | o |
Dimensions
emperature Control Range Chart
Range showed a correlation between temperature and ambient temperature the unit can be configured.
Temperature control accuracy of this unit (+- 0.5 °C) is applied to the set temperature within this range.
[Range: temperature control *2]
Although outside the scope of warranty (+- 0.5 °C) temperature control accuracy, range and showed a correlation of temperature and ambient temperature the unit can be configured.
*Measurement conditions
AC100V 60Hz (1) single-phase power supply:
Ambient humidity: 40% RH (2)
Blowing air volume: 1.0m 3 / min (3)
Sensor is mounted in the body of the performance of the outlet air outlet body (4)
The body, without mounting the fan duct (5)