Apiste Precision Air PAU-AZ1800SE
Xuất sứ: Apiste
Nhà cung cấp: PITESCO Viet Nam
Hãng sản xuất: Apiste
Specifications
| Cooling Method | Air-Cooled Type |
|---|---|
| Type | Temperature Controller (energy conservation) |
| Cooling Capacity (W) | 1300/1500 |
| Heating Capacity (W) | 1900/2100 |
| Temperature Control Precision (°C) | +-0.1 |
| Setting Temperature Range (°C) | 11~42 |
| Use Area Temperature (°C) | 15~35 (change in temperature gradient: within 1°C/1h) |
| Use Area Humidity (%RH) | 15~85(change in temperature gradient: within 5%/1h) (No condensation) |
| Processed Air Volume (m2/min)(50Hz) | 4.8/5.0 |
| External Dimensions(mm) | H1065×W400×D650 |
| Volume (kg) | 75 |
| Coating Color | Ivory(JPMA: Semi-gloss Y22-85B) |
| Blower Duct Connection Diameter (mm) | φ100 with damper |
| Rated Voltage (V) | Three-phase AC200 |
| Consumption Current (A) | 3.1/2.6 |
| Wattage (W) | 650/750 |
| Drain Discharge Water Connection Diameter (mm) | 20A Female socket (Rp3/4) |
| Coolant | HFC-134a 290g |
| Exhaust Air Volume (m3/min) | 10/12 |
| Safety Circuit/Main Circuit | Earth leakage circuit breaker(10A 30mA) |
| Safety Circuit/Blower | Overcurrent relay, delay timer (3 minutes), surge absorber, thermal overload protector |
| Safety Circuit/Compressor | Anti-freezing mechanism cooler prevention, overcurrent relay, motor protectors, surge absorber |
| Output/Main Unit Malfunction Output | No-voltage contact a (AC250V / 2A / Resistive load) |
| Output/Temperature Control Top-Bottom Limit Alarm | No-voltage contact a (AC250V / 2A / Resistive load) |
Dimensions

Temperature Control Range Chart
Range showed a correlation between temperature and ambient temperature the unit can be configured.
Temperature control accuracy of this unit (+- 0.5 °C) is applied to the set temperature within this range.
[Range: temperature control *2]
Although outside the scope of warranty (+- 0.5 °C) temperature control accuracy, range and showed a correlation of temperature and ambient temperature the unit can be configured.
*Measurement conditions
AC100V 60Hz (1) single-phase power supply:
Ambient humidity: 40% RH (2)
Blowing air volume: 1.0m 3 / min (3)
Sensor is mounted in the body of the performance of the outlet air outlet body (4)
The body, without mounting the fan duct (5)




Mr. Hà
live:ha_1652