temperature-signal-converter-umu-100-r-with-relay-bo-chuyen-doi-tin-hieu-nhiet-do-umu-100-r-co-role-ysi-vietnam.png

UMU-100R, Temperature signal converter UMU-100 R with relay, Bộ chuyển đổi tín hiệu nhiệt độ UMU-100 R có rơle YSI VietNam.

 

Temperature signal converter for PT 100 sensors / Connection for 2-, 3- or 4-wire connection

also for thermocouples  / additional current and voltage inputs

The signal converter UMU 100 is a transmitter suitable for the evaluation of PT 100 sensors as well as thermocouples (K, J, etc.). The UMU 100 signal converter is safe to operate and prevents failure of a machine or production plant. The signal converter has both a current output and a voltage output. Optionally, the signal converter can be equipped with two relay outputs so as to reach an alarm level, e.g. to activate a signal light. Due to the galvanic isolation, the supply voltage does not affect the measured signal and makes the signal converter a safe and accurate measuring instrument, which can be used universally during operation.


- for PT 100 sensors and thermocouples
- error indication on the display
- universal power supply 
- galvanic isolation of the inputs and outputs
- with 2 alarm relays
- with current and voltage input
- with current and voltage output
- configurable via detachable display (optional)

Technical Data 
Input Measuring range Accuracy
PT 100 -200 ... 850 °C / -328 ... 1562 °F ± 0.2 °C
Linear resistance 0 Ω ... 10 kΩ ± 0.1Ω  
Potentiometer 10 Ω ... 100 kΩ ---
Thermocouples (depending on the type) - 200 °C ... 2300 °C / -328 ... 4172 °F ± 2 °C
Current (freely programmable)

0 mA ... 20 mA

4 mA ... 20 mA

± 4 µA
Voltage (freely programmable)

0 V ... 1 V DC

0.2 V ... 1 V DC

0 V ... 5 V

1 V ... 5 V

0 V ... 10 V

2 V ... 10 V

± 20 µV
Output Measuring range Load
Current

0 mA ... 20 mA

4 mA ... 20 mA

20 mA ... 0 mA

20 mA ... 4 mA

maximal 

20 mA, 800 Ω, 16 V DC

Voltage 

0 V ... 1 V DC

0.2 V ... 1 V DC

0 V ... 5 V

1 V ... 5 V

0 V ... 10 V

2 V ... 10 V

1 V ... 0 V DC

1 V ... 0.2 V DC

5 V ... 0 V

5 V ... 1 V

10 V ... 0 V

10 V ... 2 V

min. 500 kΩ
Relay (close, open, hold)

Maximum voltage: 250 V RMS

Maximum current: 2 A AC or 1 A DC

Maximum power (AC): 500 VA 

General technical data
Supply voltage

24 V AC ... 230 V AC / 50 Hz ... 60 Hz

24 V DC ... 250 V DC

Max. input ≤ 2.5 W
Response time (0% ... 90% / 100% ... 0%)

Temperature input: ≤ 1 s

Current / voltage input: ≤ 400 ms

Calibration temperature 20 ... 28 °C / 68 ... 82 °F
Max. humidity 90% r.H.
Dimensions with front display (H x W x D) 109 x 23.5 x 116 mm / 42.9 x 9.2 x 45.6"
Dimensions without front display (H x W x D) 109 x 23.5 x 104 mm / 42.9 x 9.2 x 40.9"
Protection

Housing: IP 50

Clamp: IP 20

Weight 175 g / 6 oz

Anschlussarten des Signalkonverter UMU 100

Here you can see the connection types of the temperature transmitter UMU-100R