flow-switch-ub1.png

Flow Switch UB1, UB1-025HM/K, UB1-032EM/K,

● Can be used from nominal width DN 25..200

● Micro switch with gold-plating for small currents, and silver-plating for larger currents

● Visual function control through transparent

Handling and operation

Note

● Attention! Paddle fixing unsecured. For critical conditions (e.g. vibration), fit a bolted fixing.

● Include straight calming section of 10 x DN in inlet and outlet

● If the media are dirty, install a filter.

● It must be ensured that the values given for voltage, current, and power are not exceeded.

● When switched on, a load must be connected in series.

● The electrical details apply to ohmic loads. Capacitive and inductive loads must be operated using a protective circuit.