dpt-r8-hk-intruments-vietnam.png

DPT-R8 HK Instruments Vietnam

Field adjustable, multi-range differential pressure transmitters for air

DPT-R8 series differential pressure transmitters are engineered for building automation in the HVAC/R industry. The most technologically advanced transmitters on the market measuring static and differential pressure, with field selectable units, range and output, all in a single device.

DPT-R8 series devices include:
• Multiple measurement units, field selectable via jumper, including: inWC, mmWC, Pa, mbar.
• 8 field selectable measurement ranges, unidirectional or bi-directional, selectable via jumper.
• Proportional output options including: voltage (0–10 V) and current (4–20 mA).

Technical details

Accuracy (from applied pressure):
(models 250 and 2500)
Pressure < 125 Pa = 1 % + ±2 Pa
Pressure > 125 Pa = 1 % + ±1 Pa
Accuracy (from applied pressure): 
(model 7000)
Pressure< 125 Pa = 1.5 % + ±2 Pa
Pressure > 125 Pa = 1.5 % + ±1 Pa
Zero point calibration: automatic with autozero element (-AZ) or by pushbutton
Measuring units: Pa, kPa, mbar, inchWC, mmWC, psi
Supply voltage: 24 VDC ±10 % / 24 VAC ±10 %
Power consumption: < 1.0 W (< 1.2 W with output current 20 mA)
Output signals (3-wire): 0…10 VDC, Load R minimum 1 kΩ 
4…20 mA, maximum load 500 Ω
Operating temperature: -10…+50 °C (with autozero calibration -5...+50 °C) -40…+50 °C (-40C model)
Response time: 0.8 / 4 s
Protection standard: IP54
  inWC models: ETL marking, standard IEC61010-1

DPT-R8

Example 
DPT2500-R8-AZ-D

Model

Product series

DPT
Differential pressure transmitter
DPT

Measuring ranges

250
-150...+150 / -100...+100 / -50...+50 / -25...+25 / 0...25 / 0...50 / 0...100 / 0...250 Pa
2500
-100...+100 / 0...100 / 0...250 / 0...500/ 0...1000 / 0...1500 / 0...2000 / 0...2500 Pa
7000
0...1000 / 0...1500 / 0...2000 / 0...2500 / 0...3000 / 0...4000 / 0...5000 / 0...7000 Pa
1
-0.1…+0.1 / -0.25...+0.25 / -0.5...+0.5 / -1…+1 / 0…0.1 / 0…0.25 / 0…0.5 / 0…1 inWC
10
-0.5…+0.5 / -2.5...+2.5 / -0.5...+0.5 / 0…0.5 / 0…1 / 0…2.5 / 0…5 / 0…10 inWC
30
-5.0…+5.0 / -10...+10 / -15...+15 / 0…10 / 0…15 / 0…20 / 0…25 / 0…30 inWC
2500

Model type

-R8
Eight measuring ranges
-R8

Zero point calibration

-AZ
With autozero calibration
 
Standard with pushbutton manual zero point calibration
-AZ

Display

-D
With display
 
Without display
-D

Span point calibration

-S
Span point calibration
 
Without span point calibration
-S