SMALL COMPACT THERMOSTAT
KTO 011 / KTS 011
Switch temperature difference | 7K (±4K tolerance) |
---|---|
Sensor element | thermostatic bimetal |
Contact type | snap-action contact |
Service life | > 100,000 cycles |
Max. switching capacity | 250VAC, 10 (2) A / 120VAC, 15 (2) A DC 30W at 24VDC to 72VDC |
Max. inrush current | AC 16A for 10 sec. |
Connection | 2-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm² (AWG 14) stranded wire1 1.5mm² (AWG 16) |
Mounting | clip for 35mm DIN rail, EN 60715 |
Casing | plastic according to UL94 V-0, light grey |
Dimensions | 60 x 33 x 43mm |
Weight | approx. 40g |
Fitting position | variable |
Operating/Storage temperature | -45 to +80°C (-49 to +176°F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type | IP20 |
¹ When connecting with stranded wires, wire end ferrules must be used.
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.
Setting range | Art. No. Contact breaker (NC) | Art. No. Contact maker (NO) | Approvals | |||
---|---|---|---|---|---|---|
0 to +60°C | 01140.0-00 | 01141.0-00 | VDE | - | - | EAC |
-10 to +50°C | 01142.0-00 | 01143.0-00 | VDE | UL File No. E164102 | - | EAC |
+20 to +80°C | 01159.0-00 | 01158.0-00 | VDE | UL File No. E164102 | CSA | EAC |
+32 to +140°F | 01140.9-00 | 01141.9-00 | VDE | UL File No. E164102 | CSA | EAC |
+14 to +122°F | 01142.9-00 | 01143.9-00 | VDE | UL File No. E164102 | CSA | EAC |
0 to +60°C | 01146.9-00 | 01147.9-00 | VDE | UL File No. E164102 | CSA | EAC |