hsav-dungs-vietnam-hsav-dungs-combustion-controls-vietnam.png

DUNGS , DUNGS Vietnam , DUNGS Viet nam ,  DUNGS COMBUSTION CONTROLS , DUNGS COMBUSTION CONTROLS Vietnam

Technical description

The DUNGS manual operated shut-off valve

HSAV, HSAV/5 is semi-automatic as per EN 161 for gas burners and gas appliances.

-Max. operating pressure: 500 mbar / 50 kPa (HSAV/5) or 1.5 bar / 150 kPa (HSAV)

-Class A, Group 2 as per EN 161

-normally closed

-

Fast closing

- manuall opening only when operating

voltage applied

- DC solenoid, rectifier wiring with radio interference suppression in terminal box

-

Mountable closed position signal con

-tact to monitor closed position of valve

-

Tube thread as per ISO 7/1

-Flange connection as per DIN EN 1092-1

- Reliable function, rugged and maintenance-freePrinted in Germany • Edition 01.18 • Nr. 214 758

Application

The DUNGS manual operated shut-off valve HSAV... is suitable for gases of families 1, 2, 3 and other neutral gaseous media. The

manual oporation shut-off valve is used for shut-off and release of gas supply to gas burners and gas appliances. The shut-off valve can only be opened manually when the operating voltage is applied.

Approval

EC type testing certificate as per:

EC-Gas Appliances Regulation

Approvals in other important gas consuming countries.

2 ... 6

H SAV

Single-stage solenoid valve, normally closed. Manually opening with operating voltage applied, fast

closing.

HSAV/5

Single-stage solenoid valve, normally closed. Manually opening with operating voltage applied, fast

closing. Closed position signal contact mountable.

Specifications

Nominal diameters

Pipe thread as per ISO /71

Flange

Max. operating pressure

Solenoid valve

Closing time

Opening

Materials of gas-conveying parts

Ambient temperature

Installation position

Dirt trap

Measuring/ignition gas connection

Voltage/frequency

Rating / power consumption

Switch-on duration

Degree of protection

Electrical connection

Closed position signal contact

Accessories

DN 65 80 100 Rp 3/4 1 11/2 2

Connection flange (PN 16) as per DIN EN 1092-1

HSAV/5: 500 mbar (50 kPa), HSAV: 1.5 bar (150 kPa)

Valve as per EN 161, Class A, Group 2

< 1 sec

Manual, when operating voltage applied

Housing:aluminium, steel, brass

Seals:NBR basis -15°C to +60°C

Solenoid from vertically upright to horizontally lying - refer to operating and mounting instructions Sieve installed, mesh width 1 mm G 1/4 ISO 118, on both sides in inlet section, additionally G 3/4 on inlet side, from size DN 65 (flange) upwards

50-60 Hz, 230 V AC, -10% +15%, further voltages on request See type overview

100 % IP 54, IP 65 on request

At screw terminals via PG 11 cable entry

Plug connection as per DIN EN 175 301-803, can be retrofitted

Type K01/1 (DIN-tested), mountable on HSAV 5.../5

K01 closed position signal contact, see Datasheet 12.01

211 202

Equipment plug for line socket as per DIN EN 175 301-803

215 733