for-valve-controller-potentiometer-gpm-010p-r.png

“ GPM “ Potentiometer for Valve Actuator Controller is intended to use remote setting control for one 
or several units connecting with Valve Controller by manual way in Air handling facilities system.
If User set Setting Knob at desired setting location, it can be controlled by combination 
with Damper Actuator or Valve Actuator.

 

 
TYPE   for Panel (GPM-010P), for Room(GPM-010R)
  SUPPLY VOLTAGE   AC24V±10%
  FREQUENCY   60Hz
 POWER CONSUMPTION   1VA
  OUTPUT SIGNAL   0 ~ 10 VDC (factory setting)
 SETTING RANGE   0 ~ 100%
 CONNECTING NUMBER OF ACTUATOR   6EA (for max. 6 Actuators)
 PANEL CUTTING SIZE   Hole 9Ø
  AMBIENT TEMPERATURE   1) On Operation : -10 ~ +50℃
 PROTECTION CLASS ENCLOSURE   IP30
  WEIGHTL   0.07 Kg

 

 
 In case of installing on Panel, make the hole for 9 mm (diameter) first. 
 Unscrew the nut of potentiometer axis, fix axis to the hole from inside to outside of Panel.
 Attach Setting Knob to axis on 0 (zero) point setting. Power source is AC 24V.
 In case of using several actuators combination, it's preferable to decide capacity of transformer after collecting each Actuator's power consumption